High Temperature Exhaust (FA/109-01)
June 15th, 2001
"Many are never used; some are used just once; others are used all the time." What are they? They're high temperature exhaust fans.
High temperature exhaust fans can be grouped into two general categories: emergency smoke evacuation and process ventilation. Generally speaking, emergency smoke evacuation fans may never be used, but they must be installed and be capable of exhausting high temperature air and smoke in the event of a fire. In contrast, high temperature process ventilation requires continuous duty exhaust of high temperature air, fumes or particulate. Both application types are uniquely different requiring special construction and system design considerations. In this article, we will examine both types of exhaust applications, looking first at the emergency smoke exhaust category.
Emergency Smoke Exhaust
Since emergency smoke exhaust deals with life-safety issues, there are governing bodies in place that identify and regulate specific design and performance standards. The administration and organization of the various governing bodies is subject to modification based on the needs of the industry. Currently, four such agencies are Industrial Risk Insurers (IRI), Southern Building Code Congress International, Inc (SBCCI), the National Fire Protection Association (NFPA), and Underwriters Laboratories, Inc. (UL).
![]()
IRI insures properties all over the world based on an informational manual,
which details the construction requirements that belt drive emergency heat and
smoke exhausters must meet in order to be covered by IRI.
SBCCI
is a not-for-profit organization of government officials from the United States
and several foreign governments, which serves a strong leadership role in the
delivery of model building codes.
The purpose of the NFPA can be summarized into three main categories. First,
NFPA promotes the science and improves the
methods of fire protection and prevention, electrical safety, and other related
safety goals. Secondly, it obtains and circulates information on these subjects.
And thirdly, it secures the cooperation of its members and the public in establishing
proper safeguards against loss of life and property.
The fourth organization is Underwriters Laboratories, Inc.. UL is a non-profit,
independent organization that maintains and
operates laboratories for examination and testing of devices, systems and materials
to determine their relation to life, casualty hazards and crime prevention.
UL has three safety standards that apply to emergency smoke exhaust products.
UL705 is concerned with the mechanical and electrical construction to insure
safe operation. All electrical components (motor, wiring, switches, enclosures,
etc.) must be UL-listed. UL793 is concerned with the lifting mechanism for the
butterfly dampers and the fusible link. In order for a product to be listed
in the UL Directory under "Power Ventilators for Smoke Control Systems,"
it must meet the requirements of both UL705 and UL793. Additionally, UL must
witness a full-scale test of a fan operating for the required time at the specified
elevated and temperature.
Inline smoke exhaust fans, like Greenheck's TBI, can be listed in the UL directory
under "Power Ventilators for Smoke Control Systems" without having
to meet UL793, because inline fans do not require butterfly dampers since they
are not mounted in an upblast configuration. Inline smoke exhaust fans are tested
following ASHRAE
Standard 149-200 "Laboratory Methods of Testing Fans Used to Exhaust Smoke
in Smoke Management Systems".
So what makes one fan more capable of sustaining higher temperatures than another
fan? Each model has a recommended maximum operating temperature based on the
construction materials, drive components, and airflow characteristics. The limiting
temperature is determined to be the highest temperature that any component of
the fan assembly will reach during any operating cycle. Similarly, the maximum
operating temperature is typically determined to be the lowest temperature that
begins to exceed the capacity of any one component. For example, in some cases
the bearings may be the limiting component, while in other cases the fan's impeller
construction material may be the limiting component.
The construction material is perhaps the most obvious element of the fan to
consider when dealing with a high-temperature application. In general, aluminum
withstands maximum temperatures up to 250ºF, standard carbon steel up to
750ºF, and 316 stainless steel up to 1000ºF. Critical components are
many times constructed of ferrous materials to withstand the higher temperatures.
If temperatures were to exceed 300ºF, for example, aluminum would be eliminated
as a construction material option. Other construction considerations include
bearing type, drive component selections, means of ventilation and cooling of
the drive components, and insulation options.
The most common way of simplifying construction and component specifications
to accommodate high temperature applications is to maintain separate categories
based on the specified temperature range and time requirements. Greenheck for
example has four "Heat Option Packages" for high temperature operation.
Heat Option I construction is designed for continuous operation between 200ºF
and 500ºF. Heat Option II construction meets specifications requiring the
fan to exhaust 500ºF air for a minimum of four hours in an emergency smoke
removal situation per IRI requirements. Heat Option III construction meets the
specifications requiring the fan to exhaust 1000ºF air for a minimum of
15 minutes in an emergency smoke removal situation per SBCCI. This construction
also surpasses the IRI requirements for 500ºF for a minimum of four hours.
Heat Option IV construction meets specifications for UL Listed "Power Ventilators
for Smoke Control Systems." This includes the IRI requirement of 500ºF
for a minimum of four hours, the SBCCI requirements of 1000ºF for a minimum
of 15 minutes, and the Snow Load Test for butterfly dampers in UL-793.
While it may be tempting to choose a higher heat option than necessary "just to be safe", doing so can add considerable and unnecessary cost to the job. For example, selecting HT Option III when HT Option II is adequate adds insulation and high temperature bearings. These items would be considered "overkill" and add unnecessary extra costs.
|
High Temp Options
|
||||
| High Temp Construction Features |
HT Option I |
HT Option II
|
HT Option III
|
HT Option IV
|
| 165-degree fusible link damper lifters |
X
|
X
|
||
| 165-degree fusible link damper lifters(capable of lifting 10 lbs per square foot) |
X
|
|||
| Vented belt and bearing tube |
X
|
X
|
X
|
X
|
| Insulated bearing plate, bearing cover and belt tube |
X
|
X
|
||
| Steel damper blades |
X
|
X
|
X
|
X
|
| Dual drives |
X
|
X
|
X
|
X
|
| High temperature bearings |
X
|
X
|
||
| Copper lubrication lines |
X
|
|||
| High temperature aluminum paint |
X
|
|||
| Heat slinger |
X
|
|||
| UL label for "Power Ventilators for Smoke Control Systems" |
X
|
|||
The above chart summarizes how the fan construction and components vary among
Greenheck's heat options. Note that Heat Option I is specified for continuous
duty high temperature applications, while Heat Options II, III & IV are
normally for emergency smoke exhaust
![]() |
|
Greenheck's TBI test set-up. UL-witnessed inline smoke exhaust test at Greenheck's test facilities. As a result of these tests, Greenheck's TBI was the first tube axial inline fan in the industry that is UL listed as a Power Ventilator for Smoke Control Systems. |
In addition to the general construction material of the fan, other considerations
can be made to increase the limiting temperature. One of the most critical components
of the fan are the bearings. So naturally if the bearings are kept out of the
hot airstream they are less susceptible to the effects of the high temperature,
and therefore the air temperature can be higher than the limiting temperature
of the bearings. Inline fans inherently have drive components in the airstream.
In such cases, the unit can sometimes be designed so that cooler outside air
is drawn over the drive components, providing some additional cooling. Incorporating
this type of external cooling is one of the main reasons Greenheck's medium
pressure tube axial inline fan (TBI) can be used for high temperature exhaust
applications.
There are, however, some arrangements that don't allow for the incorporation
and benefits of external cooling. For instance, fans in arrangement 3 have the
wheel suspended in-between the two bearings. Consequently, one or both of the
bearings will always be located in the airstream. Similarly, direct drive fans
are limited by the maximum operating temperature of the motor, since the motor
is located directly in the hot airstream. That is why most often high temperature
exhaust fans are required to be belt driven units; typically the motor is the
temperature-limiting component of the unit when it is installed in the airstream.
Another common variation to the standard fan design is the addition of insulation.
The bearing mounting plate, bearing cover and belt tube are the most likely
components to be insulated for a high temperature application. Greenheck automatically
includes insulation for these components on all fans specified with either HT
Option III or HT Option IV.
It is important to understand that emergency smoke exhaust fans are designed
to operate effectively for the temperature and time limits stated as long as
the power supply to the fan is not terminated. Since they are not designed to
sustain higher temperatures for continuous use, exposure to the extreme high
temperatures caused by a fire likely would destroy some or all parts of the
fan once the time design limit has elapsed, rendering it incapable of future
operation.
High Temperature Process Ventilation
Fans that are built for continuous high temperature ventilation have many of
the same construction features and options as those built for emergency smoke
exhaust. For example, both are typically constructed of higher temperature ferrous
materials, have high temperature bearings, have the motor and drive installed
either out of the airstream or with some type of additional cooling capabilities,
and incorporate some heat shielding or insulation.
There are, however, some distinct differences between the fan designs for the
two application categories. One of the most common applications for which continuous
duty high temperature exhaust fans are specified is commercial kitchen ventilation.
Fans that are specified for continuous operation at higher temperatures need
to be carefully selected taking into account air density corrections. Although
a fan will move the same amount of air at two different temperatures, the static
pressure and horsepower requirements can change drastically as the density of
the air varies with changing temperatures. For example, if a fan moves 3,000
cfm at 70ºF it will also move 3,000 cfm at 500ºF. However, since the
hotter air weighs much less than the 70ºF air, the fan will require less
brake horsepower and will create less static pressure. (Reference "Understanding
Temperature and Altitude Corrections" in Greenheck's Product Application
FA/102-99 for further information on the effect of high temperature on fan performance.)
There are also some accessories and construction options that are incorporated
into high temperature process fans to increase the limiting temperature. For
example, a heat slinger can be installed on the shaft between the fan housing
and the inboard bearing. A heat slinger is an aluminum disc that absorbs and
dissipates some of the heat conducted along the shaft before it travels to the
bearings. Many heat slingers incorporate fans that promote additional inboard
bearing cooling because it circulates air with every rotation of the shaft.
Another common construction technique is the use of a heat gap. A heat gap is a physical gap between the bearing support structure and the hot fan housing. This separation slows the process of heat conduction to the bearings and drive components through the housing and support structure. An expansion bearing should be installed where the fan shaft is predicted to conduct enough heat that it could expand to a length greater than that of the structure to which it is secured. This allows for expansion of the shaft within the bearing due to the higher temperatures.
High temperature applications can be found in many different areas of the air movement and control industry. It is important to remember that one high temperature fan design is not suited to all applications.
The following checklist can help you specify the appropriate equipment for
the application.
o Emergency smoke evacuation or process
o What codes apply for
- Temperature (start-up and operation)
- Duration
o CFM and SP
o Fan location (inline, upblast)