Fire Suppression Systems
Every Type I commercial kitchen hood requires a UL 300 listed commercial fire
system.
Wet Chemical
Amerex KP and Ansul R-102 fire suppression systems use a potassium
based chemical extinguishing agent. The agent reacts with hot
grease to form a blanket of foam in a process called saponification
that seals the hazard depriving the fire of oxygen. These systems
are designed to protect hoods, ducts, plenums, filters, and cooking
equipment. The wet chemical system is available in two types,
Applicance Specific and Full Flood.
Appliance Specific - These systems are designed specific
to appliances and require knowledge of the cooking battery under the hood.
Specific nozzles and fusible links are chosen based on the type of appliance.
The systems use a temperature rated fusible link to hold a scissors link
together. When the fusible link melts, the scissors open and the system
is activated. This is a dedicated detection system that requires permanent
equipment placement; if the equipment is moved or changed, re-piping is
necessary.
Full Flood - Full flood systems require no prior knowledge
of the cooking battery with the exception of shelves, salamanders, and
upright broilers. Full flood systems have drops evenly spaced across the
length, the spacing is dependent on the manufacturer's UL listing. The
detection system is either a pneumatic tube that runs the full length
of the hood, or a fusible link detection with the links evenly spaced
the length of the hood. The advantage of the full flood system is that
cooking equipment can be moved and changed without having to alter the
fire suppression piping.
Dual Agent
Ansul Piranha fire suppression uses both wet chemical and water to suppress
the fire. Similar to the other systems, a wet chemical agent is
used to blanket the fire with foam, followed by water, to cool
the hazard. By cooling the area, the chance of a flare up is reduced.
Dual agent fire suppression systems are available both as appliance
specific and full flood and use a fusible link detection system.
Water Spray
The Water Spray fire suppression system is an automatic system, designed to
protect the cooking equipment, hoods, ducts, plenums, and filters
in facilities designed with wet-pipe sprinkler systems. Once activated,
the system provides a focused continuous water mist until it is
manually turned off. Water spray fire suppression only discharges
onto the fire area, not over the entire cooking battery. In 1997
UL removed the listing from the EA-1 fryer nozzles. Greenheck,
with several other manufacturers, has developed the Dual Tech
nozzle for use over fryers. The nozzle has self-contained chemical
canisters that discharge on the fryer first, followed by water.
(To order, consult Greenheck.)
Downloadable Greenheck Literature
Viewable with the Adobe Acrobat Reader
(Click here for more information or to download the Acrobat reader)
- Catalog:
- Wet Chemical - Amerex
KP Kitchen Fire Suppression Protection (377k)
- Full
Flood Wet Chemical - Amerex Zone Defense (370k)
- Wet Chemical - Ansul
R-102 (616k)
- Dual Agent -
Ansul - Piranha (452k)
- Bulletins:
- Ansulex Low
pH Liquid Fire Suppressant Ansul (134k)
- Mechanical
Sealing Adaptors Ansul (101k)
- PRX(tm) Liquid
Fire Suppressant Extinguishing Data Sheet (31k)
- Piranha Restaurant
Fire Suppression Systems Data Sheet (148k)
- Fire Protection For
Restaurant and Commercial Cooking Equipment (478k)
- Code and Standard Compliance
for Piranha (49k)
- Restaurant Fire Suppression
Systems (254k)
- Restaurant Fire Suppression
Systems Data Sheet (Model R102 Standard) (216k)
- Amerex KP Agent Data Sheet (50k)
- Specification Sheets:
- Amerex
Zone Defense (147k)
Amerex KP
(81k)
Ansul Piranha Spec
(96k)
Ansul R102 Spec (89k)