Here is a quick reference of Greenheck's UL Life Safety Damper products, including combination fire/smoke, smoke, fire, and ceiling radiation dampers.
| Model |
Fire
Rating
(hr.) |
Leakage
Class |
Maximum Size (in.) * |
Maximum
Temperature
ºF (ºC) |
Maximum
Velocity
fpm (m/s) |
Maximum
Pressure
in. wg
(kPa) |
Vertical
Blade |
Out of
Wall/Floor |
Round |
Single Side Angle/Plate (in.) |
Corridor
Ceiling |
Grille
Installtion |
Smoke
Detector |
No Flow
Smoke
Detector |
Quick
Connect
Breakaway |
Drive
Slip
Breakaway |
Security
Bars |
Greenheck
Test
Switch |
Momentary
Test |
| Horizontal |
Vetical |
Horizontal |
Veritcal |
| UL555 & UL555S Combination Fire Smoke Dampers [back to top] |
| CFSD-211 |
1.5 |
I |
24 x 24 |
|
350º (176º) |
2000 (10.2) |
4 (1) |
|
|
|
|
|
Yes |
Yes |
|
|
|
Yes |
|
Yes |
Yes |
| CFSD-212 |
1.5 |
II |
24 x 24 |
|
350º (176º) |
2000 (10.2) |
4 (1) |
|
|
|
|
|
Yes |
Yes |
|
|
|
Yes |
|
Yes |
Yes |
| FSD-211 |
1.5 |
I |
144 x 96 |
128 x 100 |
350º (176º) |
2000 (10.2) |
4 (1) |
|
|
|
144 x 96 |
80 x 50,
50 x 80, or 40 x 100 |
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| FSD-212 |
1.5 |
II |
144 x 96 |
128 x 100 |
350º (176º) |
2000 (10.2) |
4 (1) |
|
|
|
144 x 96 |
80 x 50,
50 x 80, or
40 x 100 |
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| FSD-213 |
1.5 |
III |
144 x 96 |
128 x 100 |
350º (176º) |
2000 (10.2) |
4 (1) |
|
|
|
144 x 96 |
80 x 50,
50 x 80, or
40 x 100 |
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| FSD-231 |
3 |
I |
72 x 48 |
72 x 48 |
350º (176º) |
2000 (10.2) |
4 (1) |
|
|
|
72 x 48 |
72 x 48 |
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| FSD-311 |
1.5 |
I |
96 x 50 |
128 x 100 |
350º (176º) |
3000 (15.2) up to
128 x 72 (V) or 96 x 50 (H); 2000 (10.2) all sizes |
4 (1) |
|
|
|
128 x 100 |
80 x 50,
50 x 80, or
40 x 100 |
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| FSD-311M |
1.5 |
I |
|
64 x 72 |
350º (176º) |
2000 (10.2) |
4 (1) |
|
|
|
64 x 72 |
64 x 50 or 50 x 72 |
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| FSD-311V |
1.5 |
I |
|
100 x 32 |
350º (176º) |
2000 (10.2) |
4 (1) |
Yes |
|
|
|
64 x 32 or
32 x 32 |
|
|
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
| FSD-312 |
1.5 |
II |
96 x 50 |
128 x 100 |
350º (176º) |
3000 (15.2) up to
128 x 72 (V) or
96 x 50 (H); 2000 (10.2) all sizes |
4 (1) |
|
|
|
128 x 100 |
80 x 50,
50 x 80, or
40 x 100 |
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| FSD-312M |
1.5 |
II |
|
64 x 72 |
350º (176º) |
2000 (10.2) |
4 (1) |
|
|
|
64 x 72 |
64 x 50 or
50 x 72 |
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| FSDR-511 |
1.5 |
I |
24 |
24 |
350º (176º) |
3000 (15.2) |
4 (1) |
|
|
Yes |
24 |
24 |
|
|
|
|
|
|
|
Yes |
|
| FSDR-512 |
1.5 |
II |
24 |
24 |
350º (176º) |
3000 (15.2) |
4 (1) |
|
|
Yes |
24 |
24 |
|
|
|
|
|
|
|
Yes |
|
| OFSD-211 |
1.5 |
I |
|
36 x 36 |
350º (176º) |
2000 (10.2) |
4 (1) |
|
Yes |
|
|
|
|
|
|
|
|
|
|
Yes |
Yes |
| OFSD-212 |
1.5 |
II |
|
36 x 36 |
350º (176º) |
2000 (10.2) |
4 (1) |
|
Yes |
|
|
|
|
|
|
|
|
|
|
Yes |
Yes |
| OFSD-311 |
1.5 |
I |
|
36 x 36 |
350º (176º) |
3000 (15.2) |
4 (1) |
|
Yes |
|
|
|
|
|
|
|
|
|
|
Yes |
Yes |
| OFSD-312 |
1.5 |
II |
|
36 x 36 |
350º (176º) |
3000 (15.2) |
4 (1) |
|
Yes |
|
|
|
|
|
|
|
|
|
|
Yes |
Yes |
| SEFSD-211 |
1.5 |
I |
48 x 30 |
48 x 30 |
350º (176º) |
2000 (10.2) |
4 (1) |
|
|
|
48 x 30 |
48 x 30 |
|
|
Yes |
Yes |
|
|
Yes |
Yes |
Yes |
| SEFSDR-511 |
1.5 |
I |
24 |
24 |
350º (176º) |
3000 (15.2) |
4 (1) |
|
|
Yes |
24 |
24 |
|
|
|
|
|
|
|
Yes |
|
| SSFSD-211 |
1.5 |
I |
48 x 30 |
48 x 30 |
350º (176º) |
2000 (10.2) |
4 (1) |
|
|
|
48 x 30 |
48 x 30 |
|
|
Yes |
Yes |
|
|
Yes |
Yes |
Yes |
| SSFSDR-511 |
1.5 |
I |
24 |
24 |
350º (176º) |
3000 (15.2) |
4 (1) |
|
|
Yes |
24 |
24 |
|
|
|
|
|
|
|
Yes |
|
| SSFDR-512 |
1.5 |
II |
24 |
24 |
350º (176º) |
3000 (15.2) |
4 (1) |
|
|
Yes |
24 |
24 |
|
|
|
|
|
|
|
Yes |
|
| UL555S Smoke Dampers [back to top] |
| SMD-201 |
|
I |
144 x 100
or 288 x 50 |
144 x 100
or 288 x 50 |
350º (176º) |
2000 (10.2) |
4 (1) |
|
|
|
|
|
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| SMD-202 |
|
II |
144 x 100
or 288 x 50 |
144 x 100
or 288 x 50 |
350º (176º) |
2000 (10.2) |
4 (1) |
|
|
|
|
|
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| SMD-203 |
|
III |
144 x 100
or 288 x 50 |
144 x 100
or 288 x 50 |
350º (176º) |
2000 (10.2) |
4 (1) |
|
|
|
|
|
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| SMD-301 |
|
I |
128 x 100
or 256 x 50 |
128 x 100
or 256 x 50 |
350º (176º) |
3000 (15.2) up to
128 x 72 (V) or
96 x 50 (H);
2000 (10.2) all
sizes |
4 (1) |
|
|
|
|
|
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| SMD-301M |
|
I |
|
64 x 72 |
250º (121º) |
2000 (10.2) |
4 (1) |
|
|
|
|
|
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| SMD-301V |
|
I |
|
50 x 32 |
350º (176º) |
2000 (10.2) |
4 (1) |
Yes |
|
|
|
|
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| SMD-302 |
|
II |
128 x 100
or 256 x 50 |
128 x 100
or 256 x 50 |
350º (176º) |
3000 (15.2) up to
128 x 72 (V) or
96 x 50 (H);
2000 (10.2) all
sizes |
4 (1) |
|
|
|
|
|
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| SMD-302M |
|
II |
|
64 x 72 |
250º (121º) |
2000 (10.2) |
4 (1) |
|
|
|
|
|
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| SMD-401 |
|
I |
192 x 72 |
192 x 72 |
250º (121º) |
3000 (15.2) up to
144 x 36 or
48 x 108;
2000 (10.2) all
sizes |
6 (1.5) up to
48 x 36;
4 (1) all sizes |
|
|
|
|
|
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| SMD-401M |
|
I |
36 x 36 |
36 x 36 |
250º (121º) |
2000 (10.2) |
4 (1) |
|
|
|
|
|
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| SMDR-501 |
|
I |
24 |
24 |
350º (176º) |
3000 (15.2) |
4 (1) |
|
|
Yes |
|
|
|
|
|
|
|
|
|
Yes |
|
| SMDR-502 |
|
II |
24 |
24 |
350º (176º) |
3000 (15.2) |
4 (1) |
|
|
Yes |
|
|
|
|
|
|
|
|
|
Yes |
|
| SESMD-201 |
|
I |
144 x 100
or 288 x 50 |
144 x 100
or 288 x 50 |
350º (176º) |
2000 (10.2) |
4 (1) |
|
|
|
|
|
|
|
Yes |
Yes |
|
|
|
Yes |
Yes |
| SESMDR-501 |
|
I |
24 |
24 |
350º (176º) |
3000 (15.2) |
4 (1) |
|
|
Yes |
|
|
|
|
|
|
|
|
|
Yes |
|
| SSSMD-201 |
|
I |
144 x 100
or 288 x 50 |
144 x 100
or 288 x 50 |
350º (176º) |
2000 (10.2) |
4 (1) |
|
|
|
|
|
|
|
Yes |
Yes |
|
|
Yes |
Yes |
Yes |
| SSSMDR-501 |
|
I |
24 |
24 |
350º (176º) |
3000 (15.2) |
4 (1) |
|
|
Yes |
|
|
|
|
|
|
|
|
|
Yes |
|
| SSSMDR-502 |
|
II |
24 |
24 |
350º (176º) |
3000 (15.2) |
4 (1) |
|
|
Yes |
|
|
|
|
|
|
|
|
|
Yes |
|
| HSD-401 |
|
I |
96 x 60
or 48 x 120 |
96 x 60
or 48 x 120 |
250º (121º) |
3000 (15.2) |
6 (1.5) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| UL555 Fire Dampers - Dynamic Rated [back to top] |
| DFD-110 |
1.5 |
|
30 x 30 |
36 x 36 |
|
4000 (20.3) up to
24 x 24 V; 2000 (10.2) all sizes |
4 (1) |
|
|
|
30 x 30 |
36 x 36 |
|
Yes |
|
|
Yes |
Yes |
Yes |
|
|
| DFD-150 |
1.5 |
|
48 x 36 |
72 x 48 or 60 x 60 |
|
4000 (20.3) up to
24 x 24 V; 2000
(10.2) all sizes |
4 (1) |
|
|
|
48 x 36 |
72 x 48 or
50 x 60 |
|
Yes |
|
|
Yes |
Yes |
Yes |
|
|
DFD-150 x 10
DFD-150 x 12
DFD-150 x 14
DFD-150 x 16 |
1.5 |
|
48 x 36 |
72 x 48 or
60 x 60 |
|
4000 (20.3) up to
24 x 24 V; 2000
(10.2) all sizes |
4 (1) |
|
|
|
48 x 36 |
72 x 48 or
50 x 60 |
|
Yes |
|
|
Yes |
Yes |
Yes |
|
|
| DFD-155 |
1.5 |
|
46 x 31 |
72 x 44 or
58 x 55 |
|
4000 (20.3) up to
24 x 24 V; 2000
(10.2) all sizes |
4 (1) |
|
|
|
46 x 31 |
70 x 44 or
58 x 55 |
|
Yes |
|
|
|
|
Yes |
|
|
| DFD-210 |
1.5 |
|
64 x 50 |
64 x 50 |
|
4000 (20.3) up to
32 x 50; 2000
(10.2) all sizes |
10 (2.5) |
|
|
|
64 x 50 |
64 x 50 |
|
|
|
|
Yes |
Yes |
Yes |
|
|
| DFD-230 |
3 |
|
64 x 48 |
64 x 48 |
|
4000 (20.3) up to
32 x 48; 2000
(10.2) all sizes |
10 (2.5) |
|
|
|
|
|
|
|
|
|
Yes |
Yes |
Yes |
|
|
| DFD-310 |
3 |
|
|
36 x 36 |
|
4000 (20.3) up to
24 x 24 V; 2000
(10.2) all sizes |
4 (1) |
|
|
|
|
|
|
Yes |
|
|
Yes |
Yes |
Yes |
|
|
| DFD-350 |
3 |
|
48 x 36 |
48 x 48 |
|
4000 (20.3) up to
32 x 50; 2000
(10.2) all sizes |
4 (1) |
|
|
|
|
|
|
Yes |
|
|
Yes |
Yes |
Yes |
|
|
| DFD-355 |
3 |
|
46 X 34 |
46 X 44 |
|
4000 (20.3) up to
24 x 24 V; 2000
(10.2) all sizes |
4 (1) |
|
|
|
|
|
|
Yes |
|
|
|
|
Yes |
|
|
| DFDAF-310 |
1.5 |
|
96 x 50 |
96 x 50 |
|
4000 (20.3) up to
24 x 24 V; 2000
(10.2) all sizes |
4 (1) |
|
|
|
|
|
|
|
|
|
Yes |
Yes |
Yes |
|
|
| DFDR-510 |
1.5 |
|
24 |
24 |
|
2000 (10.2) |
4 (1) |
|
|
Yes |
24 |
24 |
|
|
|
|
|
|
|
|
|
| DFDTF-210 |
1.5 |
|
96 x 72 or
32 x 96 |
96 x 72 |
|
4000 (20.3) up to
64 x 50 V or 64 x 48H; 2000
(10.2)
all sizes |
8 (2) up to 64 x 50 V or 64 x 48 H; 4(1) all sizes |
|
|
|
96 x 72 |
80 x 50 or 50 x 72 |
|
|
|
|
Yes |
Yes |
|
|
|
| ODFD-150 |
1.5 |
|
36 x 36 |
36 x 36 |
|
4000 (20.3) up to
24 x 24 V; 2000
(10.2) all sizes |
4 (1) |
|
Yes |
|
|
|
|
Yes |
|
|
|
|
|
|
|
| SEDFD-210 |
1.5 |
|
48 x 30 |
48 x 30 |
|
2000 (10.2) |
4 (1) |
|
|
|
48 x 30 |
48 x 30 |
|
|
|
|
|
|
|
|
|
| SEDFDR-510 |
1.5 |
|
24 |
24 |
|
2000 (10.2) |
4 (1) |
|
|
Yes |
24 |
24 |
|
|
|
|
|
|
|
|
|
| SSDFD-150 |
1.5 |
|
|
30 x 30 |
|
2000 (10.2) |
4 (1) |
|
|
|
|
30 x 30 |
|
Yes |
|
|
|
|
Yes |
|
|
| SSDFD-155 |
1.5 |
|
|
30 x 30 |
|
2000 (10.2) |
4 (1) |
|
|
|
|
30 x 30 |
|
Yes |
|
|
|
|
Yes |
|
|
| SSDFD-210 |
1.5 |
|
48 x 30 |
48 x 30 |
|
2000 (10.2) |
4 (1) |
|
|
|
48 x 30 |
48 x 30 |
|
|
|
|
|
|
Yes |
|
|
| SSDFD-350 |
3 |
|
|
30 x 30 |
|
2000 (10.2) |
4 (1) |
|
|
|
|
|
|
Yes |
|
|
|
|
Yes |
|
|
| SSDFD-355 |
3 |
|
|
30 x 30 |
|
2000 (10.2) |
4 (1) |
|
|
|
|
|
|
Yes |
|
|
|
|
Yes |
|
|
| SSDFDR-510 |
1.5 |
|
24 |
24 |
|
2000 (10.2) |
4 (1) |
|
|
Yes |
24 |
24 |
|
|
|
|
|
|
|
|
|
| UL555 Fire Dampers - Static Rated [back to top] |
| FD-100 |
1.5 |
|
|
48 x 48 |
|
|
|
|
|
|
|