Greenheck Coils
Installation & Maintenance
Installation
and Maintenance Manual (pdf)
This manual covers the basic installation, operation and maintenance
recommendations for coils manufactured by Greenheck Coils.
Always follow local codes and standards for the installation
of equipment and coils for the area in which the coils are to
be operated. Following are recommendations for the installation
of products manufactured by Greenheck Coils. Please read this
manual completely before installing and operating coils manufactured
by Greenheck Coils including the suggested maintenance on page
8. Care should be taken when handling Greenheck Coils to avoid
damage or personal injury.
Failure to observe these recommendations could result in premature
failure of the product and / or loss of the warranty provided.
Greenheck Coils will repair or replace any product determined
to have failed due to a manufacturing defect after proper evaluation
of the product and installation methods have been completed. Please
see complete Warranty Statement below.
Greenheck Coils reserves the right to request information concerning
the installation of products it manufactures and / or the return
of failed products to our facility for evaluation of the failure
before any warranty will be considered.
A Return Authorization Number (RA#) must be requested before
the coil is returned to our manufacturing facility. Any product
returned without RA # will not be accepted and all charges for
the shipment of the coil will be the shipper's responsibility.
The product must be crated such to prevent any damage from occurring
during shipment. Any product without sufficient crating that allows
damage to the product to occur will not be accepted and no warranty
will be provided.
Water Coil Installation Recommendations
1. Piping should be in accordance with accepted industry standards.
Always use a back up wrench on the coil connections when attaching
the piping to the coil if pipe thread connections are utilized.
2. When drainable coils are desired, tubes should be installed
in a horizontal position. Use a spirit level. If the tubes
cannot be installed level, special drain headers are available
on request.
3. Connect the water supply to the bottom connection on the air
leaving side and the water return to the top connection on the
air entering side.
4. When four connections are provided the extra bottom connection
can be used for an auxiliary manual drain connection, and the
extra top connection can be used for an automatic air vent or
the extra connections can be capped. Connecting the supply and/or
return in any other manner will result in very poor performance.
5. Water coils are not normally recommended for use with entering
air temperatures below 40°F. Glycol solutions or brines are
the only freeze-safe media for operation of water coils for low
entering air conditions.
6. When fresh and return air are to be heated or cooled by a
water coil, care should be used in the design of the ductwork
to insure thorough mixing before the air enters the coil. The
return air should always enter the bottom of the duct. Fresh air
should enter the top of the duct. The greater the distance between
the points of mixing and entrance to the coil, the better the
application.
7. Two position control valves, modulating valves, three way
valves or a combination of these controls can accomplish control
of water coils. Follow the recommendations of the control manufacturer
regarding types, sizing and locations. Face and bypass dampers
may also be used, but do not close off tightly. Air leakage in
cooling applications has no appreciable effect. In heating applications,
however, the air temperature may rise several degrees and should
be considered in system design. Low leakage dampers may be required.
8. Pipe sizes for the system must be selected on the basis of
the head [pressure] available from the circulating pump. It is
recommended that the velocity should not generally exceed 8 feet
per second and that the friction loss should be approximately
3 feet per 100 feet of pipe.
9. When cooling coils are banked two or three high, an intermediate
drain pan with plastic drain tubes extending into the main drain
pan should be installed on the air leaving side of each coil.
On high latent installations, the condensate draining from top
coils may load the lower coils with condensate, resulting in reduced
air flow and performance or condensate being blown downstream
into the ductwork. All individually installed water cooling coils
and the bottom of all cooling coil banks should be mounted in
drain pans extending at least ten inches from the leaving air
edge of the coil. A drain line trap must be installed to allow
condensate to drain freely. The drain line trap depth must be
twice the negative static pressure of the operating system for
the unit to drain correctly. Incorrect trapping can cause the
drain pan to overflow.
Note: Vent and Drain connections
are provided on Greenheck Coils water coils unless otherwise specified.
This allows the coils to be drained. Keep in mind that when draining
the coils, all water may not drain from the coil. In order to
completely drain the coil to prevent the possibility of freezing
during cold ambient temperatures, air or nitrogen pressure must
be utilized to blow any remaining water from the coil.
Steam Coil Installation Recommendations
A. General
- Provide separate supports and hangers for the coil and for
the piping. Always use a back up wrench on coil connections
when attaching piping to the coil. Coils not designed with pitched
casing or fin pack must be pitched ¼" per foot towards
the return connection at installation.
- Be certain that adequate piping flexibility is provided. Stresses
resulting from expansion of closely coupled piping and coil
arrangement can cause serious damage.
- Do not reduce pipe size at the coil return connection. Carry
the return connection size through the dirt pocket, making the
reduction at the branch leading to the trap.
- Vacuum breakers and air vents must be installed on all applications
to prevent retaining condensate or air in the coil. Generally
the vacuum breaker is to be connected between the coil inlet
and the trap. For a system with a flooded return main, the vacuum
breaker should be open to the atmosphere and the trap design
should allow venting of large quantities of air.
- Do not drip steam mains through coils.
- Insure steam pressure and condensate line pressure differential
is sufficient to allow efficient condensate removal from the
steam coil, especially when using modulating steam control valves
to control the leaving air temperature of the coil.
- Do not attempt to lift condensate without the assistance of
a condensate pump. The pressure required to lift condensate
must also be considered for sufficient pressure differential.
Check valves are also required to prevent reverse flow of condensate
back into the coil.
- Entering air temperatures should not be below 40° F to
insure freezing doesn't occur.
B. Traps
- Size traps in accordance with the manufacturer’s recommendations.
Be certain that the required pressure differential will always
be available. Do not undersize.
- Float and thermostatic traps are recommended for high or low-pressure
steam systems, but bucket traps may be used. Float and thermostatic
traps should be used when air venting is necessary. Bucket traps
are recommended for use with on-off control only. It is recommended
that traps be located at least 12 inches below the coil return
connection. When traps without air venting capabilities are
used, air vents are required in the system.
- Multiple coil installations-
a. Each coil or group of coils that is individually controlled
must be individually trapped.
b. Coils in series; separate traps are required for each coil,
or bank of coils, in series.
c. Coils in parallel; a single trap may be used but an individual
trap for each coil is preferred.
C. Control
- With coils arranged for series airflow, a separate control
is required on each bank, or coil, in the direction of airflow.
- On high-pressure installations, a two-position steam valve
with a face and by-pass arrangement is preferred where modulating
control is required.
- Modulating valves must be sized properly—DO NOT OVERSIZE.
Refrigerant Coil Installation Recommendations
Refrigeration coils manufactured by Greenheck Coils are shipped
with a small nitrogen holding charge. Care should be taken when
opening these coils for installation. DX coil distributors have
caps installed with soft silver solder. Once the cap is removed
and if the TEV is to be installed using anything other than soft
solder, the distributor connection should be sufficiently cleaned
with emery cloth to remove the soft solder. Follow accepted refrigeration
piping practices and safety precautions per Ashrae Standards.
If bends or 90's are necessary, long radius fittings must be used
to keep the pressure drop through the piping at a minimum. General
recommendations for component selection and line sizing follow.
Nitrogen charged and capped piping is recommended.
A. Liquid Line Sizing
All compressors have a Refrigerant Charge Limit [RCL] that must
not be exceeded. Since the RCL and pressure drop are in direct
conflict with each other, Greenheck Coils recommends that the
liquid line be sized as small as possible, while maintaining a
low enough pressure drop to ensure 5°F of sub-cooling at the
expansion valve.
B. Liquid Line Components
Greenheck Coils recommends the use of a properly sized liquid
line filter-drier, installed upstream from the expansion valve
and as close to the evaporator coil as possible. Filter-drier
selection should be based on a maximum pressure drop of 2 psi
at the design condition.
A moisture indicator / sight glass should be installed between
the expansion valve and filter-drier. The moisture indicator /
sight glass must be sized to match the size of the liquid line
at the thermal expansion valve.
A liquid line shut-off valve with an access port should be sized
with the selected liquid line OD, and installed close to the condenser,
The use of other valves, tube bends and reducers should be minimized,
since these items tend to increase pressure drop and to reduce
sub-cooling at the expansion valve. Liquid line receivers, other
than those factory-installed, are not recommended.
The Thermal Expansion Valve [TEV] must be selected for proper
size, capacity and refrigerant being used. A slightly oversized
valve will allow the unit to operate satisfactorily at low-load
conditions. An undersized valve should not be used at any time
as this will starve the evaporator of refrigerant causing insufficient
air temperatures. The use of a hot gas bypass valve should also
be considered when sizing the TEV. Select expansion valves with
external equalizer connections, and those designed to operate
against a backpressure of 20 pounds per square inch higher than
actual evaporator pressure.
The TEV must be installed directly on the evaporator coil liquid
line connection provided. The liquid distributor must be in a
vertical position. Insure that the distributor nozzle is installed
in the distributor if required and that the correct nozzle for
the refrigerant being used is installed. Sensing bulbs must be
mounted on a clean horizontal suction line close to the evaporator
outlet and insulated properly. The bulb must be tight against
the suction line at a 10 or 2 o'clock position, but take care
not to over tighten and cause damage to the sensing bulb. The
bulb should not be mounted directly on top or bottom of the suction
line.
CAUTION: Disassemble the thermal expansion valve
before completing the brazing connections. If necessary, wrap
the valve in a cool wet cloth while brazing. Failure to
protect the valve from high temperatures may result in damage
to the internal components.
C. Suction Line Sizing
Suction line tubes must be sized to maintain refrigerant vapor
velocities that are high enough to ensure good oil return to the
compressor under all operating conditions. It is necessary
to pitch horizontal suction lines toward the compressor to insure
sufficient oil return to the compressor. Traps should be provided
at the bottom of suction line risers and at 15 foot intervals
for sufficient oil return.
D. Suction Line Components
A suction line pressure tap should be installed on the leaving
side of the evaporator coil near the TEV sensing bulb location.
Accurate superheat measurement and TEV adjustment demands that
suction pressure and temperature be measured near the evaporator
coil outlet.
Suction line filter-driers are usually only necessary on systems
that have experienced a severe compressor motor burn out or other
failure that results in extremely high refrigerant temperature.
This filter-drier should not be left in the suction line permanently.
Suction lines should be insulated completely with sufficient
wall thickness insulation for the application temperature range
being utilized.
Installation Checklist
Use the following checklist to verify that all necessary installation
procedures have been completed.
- Coils are installed with airflow in same direction as indicated
on the coil nameplate or casing.
- Suction connection is at the bottom of the suction header
on the evaporator coil, suction line is pitched towards compressor
and traps are installed in suction risers. Suction line is insulated
with correct wall thickness insulation for the temperature application
utilized.
- If stacking coils, stacking channels are properly installed
and bypass air is prevented.
- Condensate drain pans and piping is installed with a trap
in the condensate line and piping insulated and heated if installed
in applications that are below freezing.
- Clean filters are installed upstream of the condenser coil
when applicable.
- A liquid line filter-drier is installed upstream of the expansion
valve.
- A moisture indicator/sight glass is installed between the
expansion valve and filter-drier.
- A liquid line shutoff valve with access port is installed
close to the condenser.
- A schrader valve is installed in the suction line close to
the evaporator coil outlet.
- The TEV, with external equalizer connections, is installed
directly on the evaporator liquid connection, sensing bulb mounted
in the horizontal position on the suction line and insulated.
The liquid distributor must be in a vertical position.
- Piping system is leak-tested with dry nitrogen, evacuated
to 500 microns, and charged with correct refrigerant type and
amount.
- Superheat and sub cooling measurements are taken. Thermal
expansion valve is adjusted to obtain desired superheat. Desired
superheat on most applications is 8° to 12° at the outlet
of the evaporator.
Maintenance
Coil Cleaning
Coils should be kept clean to maintain maximum performance. For
operation at it's highest efficiency, the coil should be cleaned
often during periods of high cooling demand or when dirty conditions
prevail. Power should be disconnected and locked out and motors
should be covered to insure that no moisture penetrates into the
windings causing motor failure if applicable.
Remove large debris from the coils and straighten fins before
cleaning.
Clean refrigerant coils with cold water and detergent or with
one of the commercially available chemical coil cleaners. Rinse
coils thoroughly after cleaning.
CAUTION: Do not clean the coil with hot water or steam. The use
of hot water or steam as a refrigerant coil-cleaning agent will
cause high pressure inside the coil tubing and subsequent damage
to the coil.
CAUTION: Do not use acidic chemical coil cleaners. Do
not use alkaline chemical coil cleaners that, after mixing, have
a ph value greater than 8.5 without also using an aluminum corrosion
inhibitor in the cleaning solution. Failure to follow these guidelines
or the manufacturer’s instructions for use of cleaning chemicals
could result in damage to the unit.
WARNING: SOME CHEMICAL COIL-CLEANING COMPOUNDS ARE CAUSTIC,
AS WELL AS TOXIC. USE THESE SUBSTANCES ONLY IN ACCORDANCE
WITH THE MANUFACTURER’S INSTRUCTIONS. FAILURE TO DO SO COULD
RESULT IN SERIOUS INJURY, DEATH OR EQUIPMENT DAMAGE.
Fin Straightening
Coil fins may have been bent during shipping or servicing, and
should be straightened to maintain maximum heat transfer. Reduction
of the effective coil surface will correspondingly reduce coil
capacity. Always check fin appearance after any handling of the
coil and after any servicing is done near the coils.
Fin combs are sized according to number of fins per inch of the
coil. For relatively small bends that require only minor
repair, other tools may be used to evenly space the fins. Be careful
not to damage the coils.
Steam Coil Applications
A steam trap maintenance program should be implemented to insure
that steam traps are operating correctly and at maximum efficiency.
Failure to do so could result in premature failure of the coil
and loss of warranty due to condensate backing up into the coil
causing leaks or allowing the coil to freeze during low ambient
conditions if supply air drops below 40° F.
Note: Steam distributing
coils may also be called "NON-FREEZE" coils. These coils
will freeze if temperatures drop below the freezing point.
Care should be taken to insure that these coils are not operated
at or below freezing temperatures. If there is the possibility
that the coils will experience freezing temperatures, freeze safeties
should be installed in the system to prevent damage to the coils.
Any coil that has failed due to freezing temperatures will not
be covered under the standard warranty.